28000666

Tridonic 89800434 EMpowerLED PRO DIM 103 SR NiCd 45W 50V – Combination DALI Emergency Lighting Driver

89800434

SKU:89800434

Tridonic 89800434 EMpowerLED PRO DIM 103 SR NiCd 45W 50V

Output power 6 – 45 W
Constant current LED operation
300 – 1,400 mA output current in mains operation, adjustable with I-SELECT 2 PLUG in steps of 25 mA or via DALI in steps of 1 mA
Independent dimmable LED driver
Emergency lighting LED driver with DALI interface and automatic test function

£81.47
Ex.VAT
Inc.VAT£97.76

Quantity Price (each)
1 £81.47
5 £81.36
10+ £80.14

Description

Tridonic 89800434 EMpowerLED PRO DIM 103 SR NiCd 45W 50V

89800434 Description

Independent dimmable LED driver
Emergency lighting LED driver with DALI interface and automatic test function
For self-contained emergency lighting
For LED modules with a forward voltage of 20 – 50 V
SELV for output voltage < 60 V DC
Compact plastic casing with strain relief
EM = EmergencY

89800434 Properties

Output power 6 – 45 W
Constant current LED operation
300 – 1,400 mA output current in mains operation, adjustable with I-SELECT 2 PLUG in steps of 25 mA or via DALI in steps of 1 mA
Integrated emergency lighting unit
1, 2 or 3 h rated duration

Operating time selectable with dip switch (2-way)
Automatic shutdown of output if the forward voltage of the LED is out of range
Two-colour status display LED
Electronic multi-level charge system
Pulse current charging for NiMH batteries
Polarity reversal protection for battery

Power-up fading at AC
Protective features (overtemperature, short-circuit, overload, no-load, input voltage range, reduced surge amplification)
Deep discharge protection
Short-circuit-proof battery connection

89800434 Interfaces

one4all (DALI DT 1 & 6, DSI, switchDIM, corridorFUNCTION)
Terminal blocks: 45° push terminals

Batteries for the 89800434

High-temperature cells
NiCd or NiMH batteries
D, Cs, LA or LAL cells
Battery box for independent use
4 year design life
For battery compatibility refer to data sheet

https://www.tridonic.com/en/int/product/89800434

89800434 COMMON DATA

Rated supply voltage 220 – 240 V
Mains frequency 50 / 60 Hz
Overvoltage protection 320 V (for 48 h)
Leakage current (PE) < 0.5 mA
Typ. λ (at 230 V, 50 Hz, normal operation) 0.95

THD CF normal operation < 10 %
Starting time < 0.5 s from detection of emergency event
Output current tolerance 7 %
Output LF current ripple (< 120 Hz) < 2 %
Max. open circuit voltage 60.0 V

Mains voltage changeover threshold According to EN 60598-2-22
Ambient temperature ta at ≤ 40 W -5 – 50 °C
Ambient temperature ta at > 40 W -5 – 45 °C
Max. casing temperature tc 75 °C
Type of protection IP20
Lifetime up to 50000 h

If the battery is required; see our Tridonic 89800389 Pack – NiCd 3D CON for suitability.

89800434 Wiring

89800434 Wiring guidelines

• The cables should be run separately from the mains connections and mains cables to ensure good EMC conditions.
• The LED wiring should be kept as short as possible to ensure good EMC.

The max. secondary cable length is 2 m (4 m circuit), this applies for LED output as well as for I-select 2.

• The secondary wires (LED module) should be routed in parallel to ensure good EMC performance.
• Secondary switching is not permitted.
• The LED Driver has no inverse-polarity protection on the secondary side. Wrong polarity can damage LED modules with no inverse-polarity protection.
• Wrong wiring of the LED Driver can lead to malfunction or irreparable damage.
• Maximum lead length for the test switch and Indicator LED connection is 1 m.

The test switch and Indicator LED wiring should be separated from the LED leads to prevent noise coupling.
• Battery leads are specified with 0.5 mm cross section and a length of 1.3 m.
• If the optional mains switch is not used, connect S/L to L.
• To avoid the damage of the control gear, the wiring must be protected against short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.).

To ensure that a luminaire containing LED emergency units complies with EN 55015 for radio frequency conducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout.

Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads. Through wiring may affect the emc performance of the luminaire. The length of LED leads must not be exceeded. The output current depends on the forward voltage and the tolerance of the LED modules.The mains power must be removed before changing the LED load.

Tridonic are a Zumtobel Group company, founded in 1956 in Dornbirn, Austria. For more than 60 years, they have been a driving force in the development of professional lighting solutions.

Today, Tridonic is a world-leading provider of lighting technology for professional applications, including office buildings, and retail outlets, hotels and restaurants, the education industry and outdoor lighting sectors.

In Tridonics’ extensive range of energy-efficient dimmable and non-dimmable LED drivers they offer the right products for every indoor and outdoor application – from cost-efficient LED drivers in proven Tridonic quality to premium products that give you maximum flexibility and convenience.

Tridonics’ dimmable LED drivers can be controlled with different analog and digital dimming signals. Tridonic basicDIM Wireless products allow wireless control without additional wiring.

Need to know more about Tridonic 89800434 EMpowerLED PRO DIM 103 SR NiCd 45W 50V – Combination DALI Emergency Lighting Driver?

You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.







    You may also be looking for...