28000666

Tridonic 89800559 EMconverter LED BASIC 203 NiCd/NiMH 50 V

89800559

SKU:89800559

Tridonic 89800559 EMconverterLED BASIC 203 NiCd/NiMH 50V

The Tridonic 89800559 is an emergency lighting LED driver used in commercial and self-contained luminaires. It powers LED modules at 3.6V (using a NiCd or NiMH battery) during main power failures, providing 1 to 3 hours of emergency lighting.

£19.75
Ex.VAT
Inc.VAT£23.70

Quantity Price (each)
1 £19.75
5 £19.25
10+ £19.00

Description

Tridonic 89800559 EMconverterLEDBASIC 203 NiCd/NiMH 50 V

89800559 Description

Emergency lighting LED driver for manual testing
For self-contained emergency lighting
For LED modules with a forward voltage of 10 – 54 V

SELV for output voltage < 60 V DC
Low profile casing (21 x 30 mm cross-section)

For luminaire installation
Compatible with Tridonic’s LLE FLEX modules (ADV, EXC)
Nominal lifetime up to 100,000 h
EM = Emergency

89800559 Properties

Non maintained operation
1 or 3 h rated duration
Operating time selectable with plug (duration link)
Compatible with all dimmable and non-dimmable constant current LED driver (see data sheet, LED driver compatibility)

3-pole technology: 2-pole LED module changeover and delayed power switching for the LED driver
Automatic shutdown of output if LED load is out of range
Constant power output

Maximum light output for all LED modules
Electronic charge system

Deep discharge protection
Short-circuit-proof battery connection
Polarity reversal protection for battery

89800559 Batteries

High-temperature cells
NiCd (3DH4-0L4) or NiMH (3QQMH4-0LFT4) batteries
D, Cs or LA cells
4 year design life

https://www.tridonic.com/en/int/product/89800559

89800559 Common Data

Ordering data EM converterLED BASIC 203 NiCd/NiMH 50V 89800559

89800559 Technical Data

Rated supply voltage 220 – 240 V
AC voltage range 198 – 264 V
Forward voltage range LED module 10 – 54 V

Mains frequency 50 / 60 Hz
Overvoltage protection 320 V (for 48 h)
Output current Refer to data sheet

Typ. λ (at 230 V, 50 Hz) 0.6 C
Starting time < 0.25 s from detection of emergency event
U-OUT (including open- / short-circuit and double load) 60 V

Max. open circuit voltage 60.0 V
Mains voltage changeover threshold According to EN 60598-2-22
Mains surge capability (between L – N) 1 kV
Mains surge capability (between L/N – PE) 2 kV

Battery charging time (1)(2) 24 h
Ambient temperature ta -5 – 55 °C
Max. casing temperature tc 75 °C

Type of protection IP20
Lifetime up to 100000 h
Guarantee 5 years

(1) 16 h battery charging time for 2 h emergency lighting function according to AS 2293.
(2) 12 h battery charging time for 2 h emergency lighting function when used with NiCd and NiMH batteries.

89800559 Other Information

89800559 Standards

• EN 61347-1
• EN 61347-2-13
• EN 61347-2-7
• EN 55015
• EN 61000-3-2
• EN 61000-3-3
• EN 61547
• EN 60068-2-64
• EN 60068-2-29
• EN 60068-2-30
• EN 62384
• according to EN 50172
• according to EN 60598-2-22

Glow-wire test

According to EN 61347-1 with increased temperature of 850 °C passed.

Insulation and electric strength testing of luminaires

Electronic LED-drivers can be damaged by high voltage. This has to be considered during the routine testing of the luminaires in production. According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, each luminaire should be submitted to an insulation test with 500 VDC for 1 second. This test voltage should be connected between the interconnected phase and neutral terminals and the earth terminal.

The insulation resistance must be at least 2 MΩ.

As an alternative, IEC 60598-1 Annex Q describes a test of the electrical strength with 1,500 VAC (or 1,414 x 1,500 VDC). To avoid damage to the electronic devices this test must not be conducted.

Thermal details and lifetime

89800559 Wiring

Lifetime

Average lifetime 50,000 hours under rated conditions with a failure rate of less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.

The emergency lighting LED driver is designed for a lifetime stated above under reference conditions and with a failure probability of less than 10 %.

The relation of tc to ta temperature depends also on the luminaire design.

If the measured tc temperature is approx. 5 K below tc max., ta temperature should be checked and eventually critical components (e.g. ELCAP) measured. Detailed information on request.

Installation / Wiring

Wiring diagram

One or more LED modules with a total forward voltage of 10 to 54 V can be connected to the EM converterLED 50V module. These LED module(s), marked with “Emergency” are operated in emergency mode from the associated battery. In normal mains mode all LED modules are operated by the LED driver from the mains supply.

Use of the test switch:
For checking the device function press the test switch for a minimum of 3 seconds.

89800559 Wiring type and cross section

Solid wire with a cross section of 0.5 – 1.5 mm². Strip 8 – 9 mm of insulation from the cables to ensure perfect operation of terminals.

Wiring: LED module/LED driver/supply

Loose wiring

Loosen wire through twisting and pulling or using a Ø 1 mm release tool

89800559 Wiring guidelines

• The LED terminals, battery, indicator LED and test switch terminals are classified as SELV (output voltage < 60 V DC). Keep the wiring of the input terminals separated from the wiring of the SELV classified terminals or consider special wiring (double insulation, 6 mm creepage and clearance) when these connections should be kept SELV.

• The output to the LED is DC but has high frequency content, which should be considered for good EMC compliance.
• Separate LED leads from the mains and DALI connections and wiring for good EMC performance.
• Maximum lead length on the LED terminals is 3 m. For a good EMC performance keep the LED wiring as short as possible.

• Route the secondary wires (LED module) in parallel to ensure good EMC performance.
• Maximum lead length for the Test switch and Indicator LED connection is 1 m. Separate the test switch and Indicator LED wiring from the LED leads to prevent noise coupling.
• Battery leads are specified with 0.5 mm cross section and a length of 1.3 m
• Protect the wiring against short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.) to avoid the damage of the control gear.

To ensure that a luminaire containing LED emergency units complies with EN 55015 for radio frequency conducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout.

Within the luminaire route the switched and unswitched 50 Hz supply wiring as short as possible and keep it as far away as possible from the LED leads.

Through wiring may affect the EMC performance of the luminaire. Do not exceed the max. length of LED leads to the LED module. Note that the length of the 89800559 leads to the LED module is added to the length of the leads from the LED driver to the 89800559 module when considering the max. permitted lead length of the LED driver.

Maximum lead length
LED 3 m (6 m loop)
Status indication LED 1 m
Batteries 1.3 m

Use of different phases

The use of different phases for switched line and unswitched line is allowed. When using different phases, the unswitched line must fail if the switched line fails. This is required to assure correct switching into emergency mode. It can be realised with a relay.

Compatibility with LLE FLEX modules

The 89800559 can be used within certain restrictions to operate constant voltage LED loads from the Tridonic LLE FLEX (ADV, EXC) product
range. A certain minimum length of the LLE FLEX is required for correct operation. Detailed information in the download area of the ST and PRO product pages at www.tridonic.com (EM converterLED manual).

Mechanical values

Housing properties
• Casing manufactured from polycarbonate.
• Type of protection: IP20
• Max. torque at the mounting screws: 0.8 Nm

Mechanical data accessories

LED status indicator
• Green
• Mounting hole 6.5 mm diameter, 1 – 1.6 thickness
• Lead length 0.3 m / 0.6 m / 1.0 m
• Insulation rating: 90 °C
• Plug connection

Test switch
• Mounting hole 7.0 mm diameter
• Lead length 0.55 m
• Plug connection

Battery leads
• Quantity: 1 red and 1 black
• Length: 1.3 m
• Wire type: 0.5 mm solid conductor
• Insulation rating: 90 °C

Battery end termination

Push on 4.8 mm receptacle to suit battery spade fitted with insulating cover

Module end termination

8.0 mm stripped insulation
Two-piece batteries are supplied with a 200 mm lead with 4.8 mm receptacle at each end and insulting covers to connect the separate sticks together.

Mechanical values

Housing properties

• Casing manufactured from polycarbonate.
• Type of protection: IP20
• Max. torque at the mounting screws: 0.8 Nm

Mechanical data accessories

LED status indicator
• Green
• Mounting hole 6.5 mm diameter, 1 – 1.6 thickness
• Lead length 0.3 m / 0.6 m / 1.0 m
• Insulation rating: 90 °C
• Plug connection

LED driver compatibility

The EM converterLED emergency unit use 3 pole technology and is compatible with most LED drivers on the market, however it is important to check that the rating of the LED driver does not exceed the values specified below:

• The max. allowed output current rating of the associated LED driver is 2 A eff (current rating of the terminals of 89800559) and 2.4 A peak (current rating of switching relays of 89800559)

• The max. allowed inrush current rating of the associated LED driver is 60 A peak for 1 ms or 84 A for 255 μs (inrush current rating of switching relay of 89800559)

• The max. allowed output voltage (U-OUT) of the associated LED driver applied to the EM converterLED output is 450 V (voltage withstand between adjacent contact of the single

switching relay of the EM converterLED)

• The max. allowed LED load of the associated LED driver is 150 W in operation. The load must be an LED module. Check compatibility with short function tests (duration of several seconds)

Functions

Duration link selection

Emergency lighting LED driver supplied with duration link in 3 hours position.

The position of the link will only be read on first power up. If it is changed afterwards both the battery and mains supply must be disconnected for 10 seconds to enable the EM converterLED to read the new link position on reconnection of the battery and mains. It will lead to a false battery failure indication if the link is changed after installation without this reset.

Status indication LED

System status is indicated by a green LED.
Note:
The status indication LED switches off if the battery does not reach the full capacity (3.6V battery voltage) within 20 – 24 hours.
If this occurs disconnect the mains voltage and operate the device in
emergency mode for approximately one hour. Afterwards apply the mains voltage again and recharge the battery for 24 hours. If the failure occurs again replace the battery.

Miscellaneous

Maximum number of switching cycles

EM converterLEDs are tested with 50,000 mains switching cycles of the associated LED driver.

Battery replacement

After a battery replacement and a subsequent full charge cycle (24 h) a duration test is mandatory to prove that with the new battery the rated
duration is achieved.

Mains-connected transformers

The EM converterLED does not contain mains-connected windings of transformers.

LED emergency modules are critical safety components designed to provide backup power (typically 3 hours) to LED fixtures during power failures, ensuring compliance with safety regulations in commercial and residential settings. These units, which often include Ni-Cd or NiMH batteries, feature deep discharge protection, automatic charging, and compatibility with various drivers for maintained or non-maintained operation.

Modes of Operation:

Maintained: The LED stays on at all times, using mains power normally and switching to battery during outages.
Non-Maintained: The LED remains off, activating only when the mains power fails.

Key Features and Functionality

Components: Modules include a rechargeable battery (often Ni-Cd or Lithium-ion), a charging circuit, and an LED status indicator.

Duration: Provide 3 hours of illumination during power cuts.

Operation Types: Available in Maintained (operates normally, stays on during power failure) and Non-Maintained (only turns on during power failure).

Voltage Range: Compatible with a wide range of LED drivers (e.g., 3-55V, 110v-240v).

Safety & Monitoring: Include deep discharge protection and a green LED indicator to show charging/functional status.

Installation: Designed for easy integration within existing luminaires, including panel lights and bulkheads.

Installation and Maintenance

Process: Requires disconnecting mains power, installing the module between the LED driver and panel, and connecting a permanent live feed for battery charging.

Testing: Manual testing via a button, with some models offering automatic self-tests (monthly/annual).

Compliance: Designed to meet safety regulations for public buildings, offices, hospitals and warehouses.

Technical Specifications

Backup Time: Typically 3 hours (180 minutes).

Compatibility: Suitable for 5-60W LED lamps.

Indicators: A green LED indicates charging/mains power; red or flashing signals usually indicate a fault or test mode.

These modules are essential in hospitals, offices, and warehouses to prevent panic and guide occupants during blackouts

Tridonic are a Zumtobel Group company, founded in 1956 in Dornbirn, Austria. For more than 60 years, they have been a driving force in the development of professional lighting solutions.

Today, Tridonic is a world-leading provider of lighting technology for professional applications, including office buildings, and retail outlets, hotels and restaurants, the education industry and outdoor lighting sectors.

In Tridonics’ extensive range of energy-efficient dimmable and non-dimmable LED drivers they offer the right products for every indoor and outdoor application – from cost-efficient LED drivers in proven Tridonic quality to premium products that give you maximum flexibility and convenience.

Tridonics’ dimmable LED drivers can be controlled with different analog and digital dimming signals. Tridonic basicDIM Wireless products allow wireless control without additional wiring.

Need to know more about Tridonic 89800559 EMconverter LED BASIC 203 NiCd/NiMH 50 V?

You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.







    You may also be looking for...