Liteplan D2N/2/80/TP40/R – High Output, Two-Part DALI-2 Addressable Emergency Conversion Kit, TUV Certified
D2N/2/80/TP40/R
Liteplan D2N/2/80/TP40/R
The D2N/2/80/TP40/R is a high out 3-hour DALI-2 addressable self-test emergency lighting conversion kit designed for remote installation through a minimum 40mm ceiling aperture. It replaces the older DNA/2/80/TP40 range.
£81.63
Ex.VAT Inc.VAT£97.96
Less Than 10 Available!
Description
Liteplan D2N/2/80/TP40/R
A 3-hour DALI-2 self-test emergency lighting conversion kit, designed to suit an extremely wide range of LED types and circuits. The D2N/2/TP40/R automatically adjusts the output LED current to provide the best match between the battery and the load, providing maximum illumination whilst ensuring full battery duration. The D2N/2/TP40/R will operate LED loads between 10-60V forward and the D2N/2/80/TP40/R will operate LED loads between 10-80V forward.
This product is fully DALI-2 compliant and in keeping with the DALI-2 Standard, if the module is commissioned without a DALI control system present, the unit will revert to standalone self-test, indicating its faults via the charge LED. This unit is designed to be mounted adjacent to the fitting in the ceiling void where there is insufficient room inside the luminaire to house the control gear. The packs will pass through a 40mm aperture.
All our batteries feature temperature monitoring. In keeping with the latest update to BS EN 61347-2-7 Their associated modules will stop charging the cells if their case temperature falls below 0°C or rises above 55°C. The emergency packs will continue to operate where required, providing their is enough capacity remaining in the battery. Our lithium iron phosphate cells feature a low self-discharge of 5% per month. The D2N range has been independently certified by TÜV to ensure that the product, has been tested for safety and that it complies with the requirements of national and international regulations.
D2N/2/80/TP40/R Specifications
TÜV Tested and Certified
DiiA Certified DALI-2 Device
2-pole Changeover Relay
Additional 3rd Pole Relay for Driver Protection
Deep Discharge Protection
Intelligent, Low Energy Charging Circuit
Extra Long Life LiFePO4 Cells
Two Part Remote Gear for 40mm Apertures
Strain Relief Module for Remote Mounting
D2N/2/TP40/R – Average Emergency Output of 5.0W
LiFePO4 Automatic Battery Protection and Recovery
The D2N/2/80/TP40/R range is supplied with strain relief cables for mounting remotely from the luminaire. The control gear and battery will pass through a 40mm, or greater aperture. A 3 hour DALI-2 self-test emergency lighting conversion kit which operates with Long Life LiFePO4 batteries. The unit is designed to suit an extremely wide range of LED types and
circuits.
The D2N/2/80/TP40/R automatically adjusts the output LED current to provide the best match between the battery and the load, providing maximum illumination whilst ensuring full battery duration.
The charger will cut-off if the Tc of the battery falls below 0 degrees C or above 55 degrees C. The product will however operate when required in emergency, should there be enough
capacity remaining in the battery.
D2N/2/80/TP40/R Specifications
• Slim Module Suitable for Smaller Apertures
• Deep Discharge Protection
• Low Power Consumption
• Long Life LiFePO4 Batteries
• Average Emergency Power – 5W
• DALI-2 Self-Test Conversion Module
• Features Battery Temperature Protection
D2N/2/80/TP40/R Technical Data
Mains Supply 230-240V AC 50/60 Hz
Power Rating (charging) * 4W 21mA λ = 0.79
Power Rating (charging) * 1.4W 12mA λ = 0.48
Duration 3-Hours
Recharge Period24-Hours
Battery Size & Type 2/LP38/S/TE
Charge Current 225mA Nominal
Module Weight 0.12Kg
Battery Weight 0.24Kg
Max Module Ta 50 °C
Max Module Tc 70 °C
Battery Temp. Parameters 0°C to 55 °C
Battery Discharge Current 900mA nominal
Discharge Voltage Limit 5 Volts
Ingress Protection IP20
Ferruled Cables0.5mm2 & 0.75 mm2
Module Dimensions (LxWxH)231 x 33.6 x 22.5 (f/c 224mm)
Battery Dimensions (LxØ) 160mm x 34.5mm
DALI-2 remote emergency kits are standalone or addressable conversion packs that convert standard LED luminaires into emergency-lit fixtures, housing the control gear and batteries in a remote remote enclosure (such as a ceiling void or external box) rather than inside the light fitting itself.
Key Features & Operation
Standard Duration: Provides 3 hours of emergency lighting operation upon mains power failure.DALI-2 Compliance: Fully compatible with DALI-2 systems and components (following Part 202 standards for self-contained emergency lighting).
Standalone Self-Test: Reverts to automatic functional and duration testing if commissioned without a DALI central monitoring system, communicating status via a bi-colour LED indicator.
Automatic Output Adjustment: Senses and adjusts output current to match the connected LED load, maximizing brightness while preserving battery life.
Battery Tech: Utilises high-temperature Lithium-ion (Li-ion) or Lithium Iron Phosphate (LiFePO4) cells with built-in deep-discharge protection.
Liteplan are the largest, privately owned emergency lighting component supplier to the UK market, whilst also shipping their products to a worldwide customer base. Established in 1994 by the late Bill Green, the company was successfully run by Bill’s right hand man, Peter Ray for many years. Peter retired in 2022 and Liteplan is now run by the next generation of Bill’s family with his son, Steve Green at the helm as Managing Director and Steve’s brother-in-law, Jonathan Bell as Director of Operations.
Their Business Development Director, Adrian Spicer is a long standing and well respected figure in the world of emergency lighting. His knowledge and stature within the industry are invaluable to them.
Liteplan’s wealth of knowledge extends many years. Their Technical Manager, David French BSc. sits on the committee at ICEL and works closely with The LIA. Their Product R&D Manager, Osman Özgür Rakibet, PhD, takes control of Liteplan’s product road map. His knowledge is steering their evolution and maintaining their position as the innovators of the emergency lighting sector.
Many of Liteplan’s engineers have worked with the company for over 20 years, constantly striving to progress through the our ever evolving CPD scheme to stay at the forefront of the ever changing world of legislation.
Liteplan proudly design all of their products in-house, making product evolution a constant and seamless process. They employ over 60 local personnel, many of whom have been with them for the majority of their existence and they also pride themselves on their unrivalled delivery satisfaction level.
Their 40,000 square foot factory enables them to carry a huge level of stock, thereby fulfilling even the largest of orders with haste. They recently acquired additional warehousing adjacent to their headquarters near London’s M25. This will fuel Liteplan’s global expansion plans for many years to come.
Need to know more about Liteplan D2N/2/80/TP40/R – High Output, Two-Part DALI-2 Addressable Emergency Conversion Kit, TUV Certified?
You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.