Vossloh-Schwabe ECXD1050.299 186763 – Huge UK Based Stock
ECXD1050.299
Vossloh-Schwabe ECXD1050.299 186763
• Compact casing shape
• For independent operation with cord grip
• For built-in without cord grip
£33.00
Ex.VAT Inc.VAT£39.60
- Description
- ECXD1050.299 Electrical characteristics
- About Constant Current DALI LED Drivers
- Vossloh-Schwabe
Description
Vossloh-Schwabe ECXD1050.299 186763
ECXD1050.299 Product features
• Compact casing shape
• For independent operation with cord grip, for integral use ECXD1050.299 186762
• For built-in without cord grip
ECXD1050.299 Functions
• The required current output can be chosen by dip switches.
• Suitable for central battery system for emergency lighting acc. to EN 50172
ECXD1050.299 Electrical features
• Mains voltage: 220–240 V ±10%
• Mains frequency: 50–60 Hz
• DC operation: 170–280 V, 0 Hz
• Push-in terminals: 0.5–1.5 mm²
• Power factor at 12 W: 0.95
• Standby losses: < 0.5 W
• Open circuit voltage (Umax.): 60 V
• Secondary side switching of LED modules is not allowed.
ECXD1050.299 Dimming
• Dimming range: 1 to 100%
• If no dimming interface is connected, brightness will stay at 100%.
ECXD1050.299 Safety features
• Protection against transient main peaks up to 2 kV (between L and N)
• Electronic short-circuit protection
• Overload protection
• Overtemperature protection
• Protection against “no load” operation
• Degree of protection: IP20
•Protection class I (built-in version); protection class II (independent version)
• SELV
• SVM: < 0.4
• PstLM: < 1
Applied standards
• EN 61347-1
• EN 61347-2-13
• EN 61547
• EN 61000-3-3
• EN 62384
• EN 55015
• IEC 62386 ed. 2 part 102/103/207
• VDE 0710-T14
ECXD1050.299 Electrical characteristics
Type ECXd 1050.299
Ref. No. 186763 ( independent )
Voltage 50–60 Hz V 220–240
Mains current mA 200
Inrush current A / μs 5 / 50
Current output DC mA (±5%) 300 -1050mA
Voltage output DC (V) 10 – 36
THD % < 10 Efficiency at full load % (230 V) > 90
Ripple 100 Hz& < 3
ECXD1050.299 Safety functions
• Transient mains peaks protection:
Values are in compliance with EN 61547 (interference immunity). Surges between L–N: up to 2 kV
• Short-circuit protection:
The control gear is protected against permanent short-circuit with automatic restart function.
• Overload protection:
The control gears have overload protection due to limitation of DC output voltage < 60 V. Please check before switch-on mains power supply that the selected LED load is suitable (see Electrical Characteristics on data sheet).
• Overheating:
The control gears have overheating protection. In case of overheating the control gear will shut down. For restart switch of the mains for 1 min. and start again. The temperature reduces the output current of the control gear in the event of overheating.
• No load operation:
The control gear is protected against no load operation (open load).
• If any of the above mentioned safety functions will be triggered, disconnect the control gear from the power supply then find and eliminate the cause of the problem.
DC and emergency lighting operation
The control gears are suitable for direct voltage operation (DC).
Reliable DC operation is guaranteed if the specified working area of LED driver is maintained.
• Light level at DC operation (EOFX): 100 % (not adjustable)
• DC range: 170–280 V
• DC operation: 3 hrs. (acc. to EN 50172)
Corridor function
To enable a predefined corridor function profile please follow the instructions below:
• Enable: press the push button for (t > 60 s) to activate the corridor function.
• Disable: disconnect the driver from mains for (t > 5 s) to deactivate the corridor function.
• 100 % light: Keep the button pressed.
• The fade off time is 30 seconds, light intensity 10%.
• The prolong time is 30 minutes, then off.
ECXD1050.299 Assembly and Safety Information
Installation must be carried out under observation of the relevant regulations and standards. Installation must be carried out in a voltage-free state (i.e. disconnection from the mains). The following advices must be observed; non-observance can result in the destruction of the LED drivers, fire and/or other hazards.
Mandatory regulations
• DIN VDE 0100
• EN 60598-1
ECXD1050.299 Mechanical mounting
• Mounting position: Built-in: Any position inside a luminaire is allowed
Independent application: Drivers with integrated cord grip are allowed to use for independent applications.
• Mounting location: LED drivers are designed for integration into luminaires or comparable devices.
Independent LED drivers do not need to be integrated into a casing.
Installation in outdoor luminaires: degree of protection for luminaire with water protection rate ≥ 4 (e.g. IP54 required).
• Degree of protection: IP20
• Clearance: Min. 0.10 m from walls, ceilings and insulation
• Surface: Solid and plane surface for optimum heat dissipation required.
• Heat transfer: If the driver is destined for installation in a luminaire. sufficient heat transfer must be ensured between the driver and the luminaire casing. LED drivers should be mounted with the greatest possible clearance to heat sources. During operation. the temperature measure at the driver’s tc point must not exceed the specified maximum value.
• Fastening: Using M4 screws in the designated holes
• Tightening torque: 0.2 Nm
• Polarity: Please ensure the correct polarity of the leads prior to commissioning. Reversed polarity can destroy the modules.
• Parallel connection: At secondary side is not allowed.
• Through-wiring: Is not allowed
• Secondary load: The sum of forward voltages of LED loads is within the tolerances which are mentioned in the Electrical Characteristics on the data sheet
ECXD1050.299 Wiring diagram
Selection of automatic cut-outs for VS LED drivers
• Dimensioning automatic cut-outs
High transient currents occur when an LED driver is switched on because the capacitors have to load. Ignition of LED modules occurs almost simultaneously. This also causes a simultaneous high demand for power. These high currents when the system is switched on put a strain on the automatic conductor cut-outs, which must be selected and dimensioned to suit.
• Release reaction
The release reaction of the automatic conductor cut-outs comply with VDE 0641, part 11, for B, C characteristics. The values shown in the following tables are for guidance purposes only and are subject to system-dependent change.
• No. of LED drivers
The maximum number of VS LED drivers applies to cases where the devices are switched on simultaneously. Specifications apply to single-pole fuses. The number of permissible drivers must be reduced by 20% for multi-pole fuses. The considered circuit impedance equals 400 mΩ (approx. 20 m [2.5 mm²] of conductor from the power supply to the distributor and a further 15 m to the luminaire).
Constant Current DALI LED drivers are advanced power supplies that deliver a stable current (not voltage) to LEDs, ensuring consistent brightness and longevity, while DALI (Digital Addressable Lighting Interface) provides precise digital control, grouping, and monitoring for complex smart lighting systems, with features like NFC configuration for fine-tuning (brightness, curves, addresses) and support for DALI-2 standards. They are essential for high-quality commercial and architectural lighting, offering flicker-free dimming and reliable performance.
How They Work
Constant Current: Instead of a steady voltage, these drivers adjust their output voltage to maintain a fixed current, vital for LEDs to prevent brightness shifts or failure.
DALI Control: A digital communication protocol allows the driver to receive commands (dim, set scenes, etc.) from a control system, enabling individual or group control.
Key Features & Benefits
Precise Dimming: Smooth, flicker-free dimming down to very low levels (e.g., 0.1%).
Digital Addressing: Each driver/luminaire gets a unique address for specific control.
Bi-directional Communication: Allows monitoring of the lighting circuit as well as control.
NFC Configuration: Near Field Communication enables easy, non-contact setup of parameters like current, groups, scenes, and dimming curves (linear/logarithmic).
DALI-2 Standard: Latest standard for improved compatibility and performance.
Versatile Applications: Suitable for downlights, strip lights, and architectural fixtures in both commercial and residential settings.
Whenever an electric light goes on around the world, Vossloh-Schwabe is likely to have made a key contribution to ensuring that everything works at the flick of a switch.
Vossloh-Schwabe has been around for more than 100 years. Headquartered in Germany, and with more than 500 employees at several production and sales sites throughout the world, Vossloh-Schwabe counts as a technology leader within the lighting sector. Top-quality, high-performance products form the basis of the company’s success.
Vossloh-Schwabe’s extensive product portfolio covers all lighting components: LED systems with matching control gear units, highly efficient optical systems, state-of-the-art control systems (Blu2Light and LiCS) as well as electronic and magnetic ballasts, ignitors and lampholders.
Vossloh-Schwabe operates based on a global, uniformly applicable quality management system. All production sites as well as the most important and largest distribution sites are also certified in accordance with ISO 9001.
The environmental management certification process in accordance with ISO 14001 was introduced in 2004 and the certification of all production sites took place at the end of 2005.
All quality relevant processes are subject to permanent monitoring and are managed using defined figures. All products are checked for compliance with the high Vossloh-Schwabe quality requirements along then entire production chain. Employees receive constant internal and external training to ensure that this standard is maintained.
Need to know more about Vossloh-Schwabe ECXD1050.299 186763 – Huge UK Based Stock?
You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.