Tridonic 28000035 PCA 1×36 T8 ECO lp Y II – Huge UK Based Stock
28000035
Tridonic 28000035 PCA 1×36 T8 ECO lp Y II
The 28000035 is a 1 x 36W T8 dimmable ballast from Austrian manufacturer Tridonic.
£34.19
Ex.VAT Inc.VAT£41.03
Description
Tridonic 28000035 PCA 1×36 T8 ECO lp Y II
28000035 Description
Processor-controlled ballast with y II inside
Highest possible energy class CELMA EEI = A1 BAT1
Noise-free precise control via DALI or
DSI signal, switchDIM or corridorFUNCTION
Nominal life up to 100,000 h (at ta 50 °C with a failure rate max. 0.2 % per 1,000 h)
Multi-lamp management
OEM-specific reserved memory areas
28000035 Interfaces
DALI
DSI
switchDIM (with memory function + selectable dimming rate)
corridorFUNCTION (3 preprogrammed profiles)
Integrated SMART interface for function with SMART Sensor 5D 19f and corridorFUNCTION plugs
28000035 Functions
Intelligent Temperature Guard (overtemperature protection)
Intelligent Voltage Guard (overvoltage indication and undervoltage shutdown)
Optimum filament heating in any dimmer setting
Disconnection of filament heating from a dimming level of approx. 90 % for maximum energy efficiency (SMART-Heating concept)
corridorFUNCTION with ambient light control
Automatically triggered emergency lighting value in DC mode, 15 %
For emergency lighting systems as per EN 50172
Automatic start after replacement of defective lamps
Automatic shutdown if the lamp is fault
28000035 Technical Data
Mains voltage range 220 – 240 V
AC voltage range 198 – 264 V
DC voltage range 176 – 280 V (lamp start ≥ 198 V DC)
Mains frequency 0 / 50 / 60 Hz
Overvoltage protection 320 V AC, 1 h
Typ. power input on standby < 0.2 W
Protective hot restart 0.5 s for AC / 0.2 s for DC
Dimming range 1 – 100 %
Lamp start possible from 1 %
Operating frequency ~ 40 – 130 kHz
Type of protection IP20
28000035 Wiring type and cross section
The wiring can be solid cable with a cross section of 0.5 to 0.75mm² for push terminal and 0.5mm² for IDC terminal. For the push-wire connection you have to strip the insulation (8–9mm).
RFI
• Connection to the lamps of the hot leads must be kept as short as possible
• Mains leads should be kept apart from lamp leads (ideally 5–10 cm distance)
• Do not run mains leads adjacent to the electronic ballast
• Twist the lamp leads
• Keep the distance of lamp leads from the metal work as large as possible
• Mains wiring to be twisted when through wiring
• Keep the mains leads inside the luminaire as short as possible
Wiring advice
The lead length is dependent on the capacitance of the cable. With standard solid wire 0.5/0.75mm² the capacitance of the lead is 30–80 pF/m.
This value is influenced by the way the wiring is made.
Lamp connection should be made with symmetrical wiring.
Hot leads (10, 11, 15, 16) and cold leads (12, 13, 14) should be separated as much as possible.
When using two or more dimmable ballasts in one luminaire with separate dimming controls, the lamp leads must be kept separate.
Sensor wires
Sensor wires must be routed separately from the lamp wires and mains cables otherwise the lighting control system may malfunction.
If separate routing is not possible (for reasons of space) shielded lamp wires and mains cables must be used.Dimmable ballasts from Tridonic have to be earthed
Tridonic are a Zumtobel Group company, founded in 1956 in Dornbirn, Austria. For more than 60 years, they have been a driving force in the development of professional lighting solutions.
Today, Tridonic is a world-leading provider of lighting technology for professional applications, including office buildings, and retail outlets, hotels and restaurants, the education industry and outdoor lighting sectors.
In Tridonics’ extensive range of energy-efficient dimmable and non-dimmable LED drivers they offer the right products for every indoor and outdoor application – from cost-efficient LED drivers in proven Tridonic quality to premium products that give you maximum flexibility and convenience.
Tridonics’ dimmable LED drivers can be controlled with different analog and digital dimming signals. Tridonic basicDIM Wireless products allow wireless control without additional wiring.
Need to know more about Tridonic 28000035 PCA 1×36 T8 ECO lp Y II – Huge UK Based Stock?
You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.