28000666

Tridonic 28001909 LCA 50W 350–1050mA DT8 lp PRE – Best Energy Savings Due To Low Stand-By Losses

28001909

SKU:28001909-8001910

Tridonic 28001909 LCA 50W 350–1050mA DT8 lp PRE

NEW: lumDATA (DALI-2 part ext. 251, 252 and 253)
Dimmable built-in constant current 2-channel LED driver with DALI-2 DT8
Dimming range 3 to 100 %
Suitable for luminaires of protection class I and protection class II (see data sheet chapter 3.4 for details)
Output current adjustable between 350 – 1,050 mA for each channel
Max. output power 50 W
Up to 89 % efficiency

£61.85
Ex.VAT
Inc.VAT£74.22

Less Than 10 Available!

Quantity Price (each)
1 £61.85
5 £59.89
10+ £58.40

Description

Tridonic 28001909 LCA 50W 350–1050mA DT8 lp PRE

28001909 Description

NEW: lumDATA (DALI-2 part ext. 251, 252 and 253)
Dimmable built-in constant current 2-channel LED driver with DALI-2 DT8
Dimming range 3 to 100 %
Suitable for luminaires of protection class I and protection class II (see data sheet chapter 3.4 for details)
Output current adjustable between 350 – 1,050 mA for each channel
Max. output power 50 W
Up to 89 % efficiency
Power input on stand-by < 0.25 W

28001909 Housing properties

Low profile metal casing with white cover
Type of protection IP20

28001909 Interfaces

one4all (DALI-2 DT8, DSI, switchDIM, corridorFUNCTION V2)
colourSWITCH
Terminal blocks: 0° push terminals

28001909 Functions

Adjustable output current in 1-mA-steps (DALI) or with resistor plug (I-SELECT 2)
Constant light output function (CLO)
colourSWITCH with predefined colours
switchDIM and colourSWITCH with memory function
Power-up fading and fade2zero
Configurable via DALI
Protective features (overtemperature, short-circuit, overload, no-load, reduced surge amplification)
Intelligent Voltage Guard (overvoltage and undervoltage monitoring)
Suitable for emergency escape lighting systems acc. to EN 50172

28001909 Benefits

Flexible configuration via companionSUITE
Application-oriented operating window for maximum compatibility
Best energy savings due to low stand-by losses
Flexible configuration via DALI and I-SELECT 2

Typical applications for the 28001909

For linear/area lighting in office applications
Tunable white application

https://www.tridonic.com/en/int/product/28001909

28001909 Common Data

Rated supply voltage 220 – 240 V
AC voltage range 198 – 264 V
DC voltage range 176 – 280 V
Mains frequency 0 / 50 / 60 Hz
Overvoltage protection 320 V AC, 48 h
Typ. current (at 230 V, 50 Hz, full load) (1)(2) 105 – 252 mA
Typ. current (220 V, 0 Hz, full load, 15 % dimming level) (2) 47 mA

Leakage current (at 230 V, 50 Hz, full load) (1)(2) < 0.5 mA
Typ. input current in no-load operation 22 mA
In-rush current (peak / duration) 29 A / 180 µs
Typ. power consumption on stand-by (3) < 0.25 W
Typ. input power in no-load operation < 0.5 W
Typ. efficiency (at 230 V, 50 Hz, full load) (2) 89 %
λ (at 230 V, 50 Hz, full load) (1) 0.97
THD (at 230 V, 50 Hz, full load) (1) < 10 %
Starting time (at 230 V, 50 Hz, full load) (4) < 0.6 s
Starting time (DC mode) (4) < 0.3 s
Switchover time (AC/DC) (5) < 0.2 s

Turn off time (at 230 V, 50 Hz, full load) < 0.02 s
Output current tolerance (1)(6) ± 3 %
Max. output current peak (non-repetitive) ≤ output current + 20 %
Output LF current ripple (< 120 Hz) ± 4 %
Output P_ST_LM (at full load) ≤ 1
Output SVM (at full load) ≤ 0.4
Max. output voltage (U-OUT) 60 V
Dimming range 3 – 100 %
Colour tuning range 2,700 – 6,500 K

Mains surge capability (between L – N) 1 kV
Mains surge capability (between L/N – PE) 2 kV
Surge voltage at output side (against PE) < 0.5 kV
Type of protection IP20
Length 360 mm
Width 30 mm
Height 21 mm

Also stocked within the multi channel series

28001910

Other information for the 28001909

28001909 Standards

EN 55015
EN 61000-3-2
EN 61000-3-3
EN 61347-1
EN 61347-2-13
EN 62384
EN 61547
EN 62386-101 (DALI-2)
EN 62386-102 (DALI-2)
EN 62386-207
According to EN 50172 for use in central battery systems
According to EN 60598-2-22 suitable for emergency lighting installations

The LED driver is designed for a lifetime stated above under reference conditions and with a failure probability of less than 10 %.

The relation of tc to ta temperature depends also on the luminaire design.

If the measured tc temperature is approx. 5 K below tc max., ta temperature should be checked and eventually critical components (e.g. ELCAP) measured. Detailed information on request.

28001909 Wiring

28001909 Wiring type and cross section

For wiring use solid wire from 0.5 – 1.5 mm².
Strip 8 – 9 mm of insulation from the cables to ensure perfect operation of terminals.

28001909 Wiring guidelines

• Run the secondary lines separately from the mains connections and lines to achieve good EMC performance.
• The max. secondary cable length is 2 m (4 m circuit), this applies for LED output as well as for I-SELECT 2.
• For good EMC performance, keep the LED wiring as short as possible.
• Secondary switching is not permitted.
• The LED driver has no inverse-polarity protection on the secondary side.

Wrong polarity can damage LED modules with no inverse-polarity protection.

• Wrong wiring of the LED driver can lead to malfunction or irreparable damage.

• In case of protection class II applications it’s recommended to separate the lamp wires of the different channels. Depending onto the luminaire construction additional actions, such as equipotential connection between driver and LED or a toroidal ferrite at the lamp wires are recommended.

• To avoid the damage of the Driver, the wiring must be protected against short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.).

Hot plug-in

Hot plug-in is not supported due to residual output voltage of > 0 V. When connecting an LED load, restart the device to activate the LED output.

This can be done via mains reset or via interface (DALI, DSI, switchDIM).

Earth connection

The earth connection is conducted as protection earth (PE). The LED driver can be earthed via earth terminal or metal housing. If the LED driver will be earthed, protection earth (PE) has to be used. There is no earth connection required for the functionality of the LED driver.

Earth connection is recommended to improve following behaviour:
• Electromagnetic interferences (EMI)
• LED glowing at stand-by
• Transmission of mains transients to the LED output In general it is recommended to earth the LED driver if the LED module is mounted on earthed luminaire parts respectively heat sinks and thereby representing a high capacity against earth.

Make sure that the LED driver is operated within the given window under all operating conditions. Special attention needs to be paid at dimming and DC emergency operation as the forward voltage of the connected LED modules varies with the dimming level, due to the implemented amplitude dimming technology. Coming below the specified minimum output voltage of the

LED driver may cause the device to shut-down. See chapter “6.8 DC operation” for more information.

28001909 Dimming

Dimming range 1 % to 100 %
Digital control with:
• DSI signal: 8 bit Manchester Code
Speed 1 % to 100 % in 1.4 s
• DALI signal: 16 bit Manchester Code
Speed 1 % to 100 % in 0.2 s
Programmable parameter:
Minimum dimming level
Maximum dimming level
Default minimum = 1 %
Programmable range 1 % ≤ MIN ≤ 100 %
Default maximum = 100 %
Programmable range 100 % ≥ MAX ≥ 1 %
Dimming curve is adapted to the eye sensitiveness.
Dimming is realized by amplitude dimming.

28001909 Software / Programming / Interfaces

Control input DALI
The control input is non-polar for digital control signals (DALI).
The control signal is not SELV. The control cable has to be installed in accordance to the requirements of low voltage installations.
Digital control with:
• DALI signal: 16 bit
• DSI signal: 8 bit

28001909 Software / programming

With appropriate software and interface different functions can be activated and various parameters can be configured in the LED driver.
The Driver supports the following software and interfaces:
Software / hardware for configuration:
• companionSUITE (deviceGENERATOR, deviceCONFIGURATOR,
deviceANALYSER)
• masterCONFIGURATOR
Interfaces for data transfer:
• Control input DALI

I-SELECT 2

By inserting a suitable resistor into the I-SELECT 2 interface, the current value can be adjusted. The relationship between output current and resistor value can be found in the chapter “Accessories I-SELECT 2 Plugs”.

If the resistor is connected by wires a consistent base insulation must be ensured. Furthermore, a max. wire length of 2 m may not be exceeded and potential interferences have to be avoided.

DC operation

In emergency light systems with a central battery supply the DC recognition function uses the input voltage to detect if emergency mode is present.

The LED driver then automatically switches to DC mode and dims the light to the defined DC level.

Without DC recognition different and more complex solutions would have to be applied in order to detect emergency mode.

DC recognition is integrated in the device as standard.No additional commissioning is necessary for activation.

The LED driver is designed to operate on DC voltage and pulsed DC voltage.

For a reliable operation, make sure that also in DC emergency operation the LED driver is run within the specified conditions as stated in chapter “4.1 operating window”.

Light output level in DC operation: programmable 1 – 100 % (factory default = 15 %, EOFi = 0.13).

The voltage-dependent input current of Driver incl. LED module is depending on the used load.

The voltage-dependent no-load current of Driver (without or defect LED module) is for:

AC: 21.8 mA (at 230 V, 50 Hz)
DC: 5 – 7 mA (at 275 – 186 V, 0 Hz)

In DC operation dimming mode can be activated.

If Dimming on DC is activated the requirements of the DC recognition function are ignored.

Even if DC is detected, the LED driver continues to behave as in AC mode
• The present dimming level is retained
• An emergency light level defined for the DC recognition function (DC level) is ignored
• Control signals via DALI continue to be executed

If Dimming on DC is activated then emergency mode is not recognised.
The device no longer automatically switches to the emergency light level.

DALI Linear Multi-Channel DT8 systems are advanced LED lighting solutions designed for precise color control (Tunable White, RGB, or RGBW) within linear fixtures, using a single DALI address to control multiple channels.

These systems, commonly used for linear architectural lighting, utilize the IEC 62386-209 standard (Device Type 8) to manage colour temperature and intensity, reducing wiring complexity and addressing, and are often available in 24V or 48V DC variants.

Key Features and Capabilities

Single Address Control: Unlike DT6 (which requires one address per channel), DT8 uses a single address to control CCT, RGB, or RGBW, significantly simplifying installation.

Multi-Channel Output: Often designed with 4 or 5 channels (PWM output) to manage RGBW or RGB+Tunable White configurations, allowing for vibrant color mixing and tunable white adjustment.

7-in-1 Flexibility: Some advanced controllers (e.g., Sunricher SR-2309PRO-5C) support 7 modes: Tc, RGBWAF, XY, 2*Tc, XY+Tc, RGB+Tc, and XY+W (DT6), allowing one device to handle various lighting requirements.

Compatibility: Fully compatible with universal DALI-2 systems and masters.

Built-in Dimming & Colour Control: Many models include push-dim functionality to control brightness, color temperature, and RGB colours without a dedicated DALI signal.

High Power Options: Available for linear applications requiring significant power, such as 300W-900W (12-36V) or 720W (48V).

Flicker-Free & Deep Dimming: Supports smooth dimming down to 0.1%, ensuring high-quality, flicker-free performance.

Tridonic are a Zumtobel Group company, founded in 1956 in Dornbirn, Austria. For more than 60 years, they have been a driving force in the development of professional lighting solutions.

Today, Tridonic is a world-leading provider of lighting technology for professional applications, including office buildings, and retail outlets, hotels and restaurants, the education industry and outdoor lighting sectors.

In Tridonics’ extensive range of energy-efficient dimmable and non-dimmable LED drivers they offer the right products for every indoor and outdoor application – from cost-efficient LED drivers in proven Tridonic quality to premium products that give you maximum flexibility and convenience.

Tridonics’ dimmable LED drivers can be controlled with different analog and digital dimming signals. Tridonic basicDIM Wireless products allow wireless control without additional wiring.

Need to know more about Tridonic 28001909 LCA 50W 350–1050mA DT8 lp PRE – Best Energy Savings Due To Low Stand-By Losses?

You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.







    You may also be looking for...