Tridonic 28000075 PC 1 x 26-42 TC TOP

The 28000075 is obsolete, now use the EL1/2X18-42TC as a suitable alternative.

• CELMA Energy Efficiency Index A2
• Nominal life-time up to 50,000 h (at ta 50 °C with a failure rate max. 0.2 % per 1,000 h)
• Large temperature range (for values see table)
• Fixed frequency operation for constant lamp current
• Lamp preheating for min. 30,000 starts without replacement of lamps
• Constant luminous lux irrespective of luctuations in mains voltage
• Designed for THD < 10 %
• For luminaires of protection class I and protection class II
• Automatic start after replacement of defective lamps (detects 1 lamp)
• Safety shutdown of defective lamps and at end of lamp life
• Push terminal for rapid automatic or manual wiring
• For emergency lighting systems as per EN 50172

https://resources.tridonic.com/PDB/Ressource/Web_TR/Archive_PDF/Ballasts_fluorescent_lamps/Fixed_output/PC_TC_TOP_18-42W_en.pdf

28000075 Technical data

Mains voltage range 220 – 240 V
AC voltage range 198 – 264 V
DC voltage range 176 – 280 V (lamp start ≥ 198 V DC)
Mains frequency 0 / 50 / 60 Hz
Overvoltage protection 320 V AC, 1 h
Defined warm start ≤ 1.6 s
Operating frequency ≥ 40 kHz
Type of protection IP20

Standards
EN 55015
EN 60929
EN 61000-3-2
EN 61000-3-3
EN 61347-2-3
EN 61347-2-4
EN 61547
according to EN 50172

Lamp starting characteristics
Warm start
Starting time ≤ 1.6 s with AC and DC operation
Cathode heating will be reduced after preheat time

AC operation
Mains voltage:
220–240 V 50/60 Hz
198–264 V 50/60 Hz including safety tolerance (±10 %)
202–254 V 50/60 Hz including performance tolerance (+6 % / -8 %)

DC operation
Mains voltage:
220–240 V 0 Hz
198–280 V 0 Hz certain lamp start
176–280 V 0 Hz operating range
Light output level in DC operation: 100 %

Emergency lighting
Use in emergency lighting installations according
to EN 50172 or for emergency luminaires
according to EN 61347-2-3 appendix J.

28000075 Wiring

28000075 Wiring type and cross section

The wiring can be in stranded wires with ferrules or solid with a cross section of 0.5–1.5 mm². Strip 9.5 mm of insulation from the cables to ensure perfect operation of the
push-wire terminals.

RFI

Tridonic ballasts are RFI protected in accordance with EN 55015. To operate the luminaire correctly and and to minimise RFI we recommend the following instructions:

• Connection to the lamps of the “hot leads” must be kept as short as possible
• Mains leads should be kept apart from lamp leads
• Do not run mains leads adjacent to the electronic ballast
• Twist the lamp leads
• Keep the distance of lamp leads from the metal work as large as possible
• Connect functional earth to the ballast
• Keep the mains leads inside the luminaire as short as possible

RFI

• Connection to the lamps of the “hot leads” must be kept as short as possible
• Mains leads should be kept apart from lamp leads
• Do not run mains leads adjacent to the electronic ballast
• Twist the lamp leads
• Keep the distance of lamp leads from the metal work as large as possible
• Connect functional earth to the ballast
• Keep the mains leads inside the luminaire as short as possible

Tridonic are a Zumtobel Group company, founded in 1956 in Dornbirn, Austria. For more than 60 years, they have been a driving force in the development of professional lighting solutions.

Today, Tridonic is a world-leading provider of lighting technology for professional applications, including office buildings, and retail outlets, hotels and restaurants, the education industry and outdoor lighting sectors.

In Tridonics’ extensive range of energy-efficient dimmable and non-dimmable LED drivers they offer the right products for every indoor and outdoor application – from cost-efficient LED drivers in proven Tridonic quality to premium products that give you maximum flexibility and convenience.

Tridonics’ dimmable LED drivers can be controlled with different analog and digital dimming signals. Tridonic basicDIM Wireless products allow wireless control without additional wiring.

Need to know more about Tridonic 28000075 PC 1 x 26-42 TC TOP?

You can email us at: sales@ledparts.co.uk or alternatively you can request a callback by completing the form below and we'll get back to you as soon as possible.







    You may also be looking for...